Figure 6-105
Line contactor control via DO 2 with feedback signal via DI 3
If the line contactor feedback signal is not available for longer than the time set in p0861, the
converter signals fault F07300.
Parameters
Number
Name
Factory setting
r0046.0…n
CO/BO: Missing enable signals
-
p0860
BI: Line contactor feedback signal
863.1
p0861
Line contactor monitoring time
100 ms
r0863.0…1
CO/BO: Drive coupling status word / control word
-
p0867
Power unit main contactor hold time after OFF1
50 ms
p0869
Configuration sequence control
0000 bin
p0870
BI: close main contactor
0
More information is provided in the parameter list.
Advanced commissioning
6.10 Energy saving
SINAMICS G120X converter
452
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC