● F30024 (temperature model overtemperature)
● F30025 (chip overtemperature)
● F30035 (air intake overtemperature)
● F30037 (rectifier overtemperature)
Precondition
Switch off the converter power supply before replacing the fan unit.
WARNING
Electric shock as a result of a residual charge in power components
After the power supply has been switched off, it takes up to 5 minutes until the capacitors in
the converter have discharged so that the residual charge is at a non-hazardous level.
Therefore, touching the converter immediately after powering off can result in electric shock
due to residual charge in the power components.
● Check the voltage at the converter connections before you replace the fan unit.
Corrective maintenance
10.2 Replacing spare parts
SINAMICS G120X converter
1056
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC