p29537
Multi-pump control disconnection lockout time / Mpc t_disc_lockout
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.000 [s]
Max:
999.000 [s]
Factory setting:
0.000 [s]
Description:
Multi-pump control-holding time switch-out: The time set in p29537 is applied as a delay time between the
disconnection of each motor.
r29538
Multi-pump control variable-speed motor / Mpc driven mtr
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the No. of the motor which is driven by drive.
Valid Value :
1 - 6
p29539
Multi-pump control pump switchover enable / Mpc sw-over enab
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Enables the multi-pump control pump switchover function.
0: Pump switchover function inhibited
1: Pump switchover function enabled
Value:
0:
Disable switchover
1:
Enable switchover
Note
With pump switchover enabled, the converter monitors the operation status of all running pumps.
If the continuous operating hours of the pump in converter operation exceed the threshold, the converter switches off
the pump and then switches in an idle pump to keep constant output power.
If the continuous operating hours of a pump in mains operation exceed the threshold, the converter switches off the
pump, switches the converter-controlled pump to mains operation, and switches in an idle pump to run in converter
operation to keep constant output power.
p29540
Multi-pump control service mode enable / Mpc SerMode enab
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Enables the multi-pump control service mode.
0: Service mode inhibited
1: Service mode enabled
Value:
0:
Disable MPC
1:
Enable MPC
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
919
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......