r29706
CO: Temperature sensor exciting current output / TempSen I_out
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Current output to temperature sensor in percent of 20mA.
Note
This CO parameter may connect to the analog output source set(e.g. p771[x]), which is the AO channel of sensor
connected.
r29707
CO: Temperature sensor resistance value / TempSen R
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [ohm]
Max:
- [ohm]
Factory setting:
- [ohm]
Description:
Display the actual resistance value of the temperature sensor.
p29708
Temperature sensor exiting current set / TempSen I_exit
Access level: 4
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [%]
Max:
100.00 [%]
Factory setting:
50.00 [%]
Description:
Sets the exciting current of temperature sensor.
p60000
PROFIdrive reference speed reference frequency / PD n_ref f_ref
G120X_DP,
G120X_PN
Access level: 2
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
6.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
1500.00 [rpm]
Description:
Sets the reference quantity for speed and frequency.
All speeds or frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
The following applies: reference frequency (in Hz) = reference speed (in ((rpm) / 60) x pole pair number)
Dependency:
See also: p2000
NOTICE
When the reference speed / reference frequency is changed, short-term communication interruptions may occur.
Parameters
7.2 Parameter list
SINAMICS G120X converter
934
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......