Table 6-23
Instance Attribute
No.
Service
Type
Name
Value/explanation
3
set
Array of
UINT8
Assembly
1 byte array
Supported ODVA AC/DC assemblies
Connection Manager Object, Instance Number: 6 hex
Supported services
Class
● Get Attribute all
● Get Attribute single
Instance ● Forward open
● Forward close
● Get Attribute single
● Set Attribute single
Table 6-24
Class Attribute
No.
Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances
Table 6-25
Instance Attribute
No.
Service
Type
Name
Value/explanation
1
get
UINT16
OpenReqs
Counters
2
get
UINT16
OpenFormat Re‐
jects
Counters
3
get
UINT16
OpenResource
Rejects
Counters
4
get
UINT16
OpenOther Re‐
jects
Counters
5
get
UINT16
CloseReqs
Counters
6
get
UINT16
CloseFormat Re‐
jects
Counters
7
get
UINT16
CloseOther Re‐
jects
Counters
8
get
UINT16
ConnTimeouts
Counters
Number of bus errors
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
229
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......