p1013[0...n]
CO: Fixed speed setpoint 13 / n_set_fixed 13
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Setting and connector output for fixed speed setpoint 13.
Dependency:
See also: p1020, p1021, p1022, p1023, r1024, r1197
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1014[0...n]
CO: Fixed speed setpoint 14 / n_set_fixed 14
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Setting and connector output for fixed speed setpoint 14.
Dependency:
See also: p1020, p1021, p1022, p1023, r1024, r1197
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1015[0...n]
CO: Fixed speed setpoint 15 / n_set_fixed 15
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3010
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Setting and connector output for fixed speed setpoint 15.
Dependency:
See also: p1020, p1021, p1022, p1023, r1024, r1197
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1016
Fixed speed setpoint select mode / n_set_fix select
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 3010, 3011
Min:
1
Max:
2
Factory setting:
1
Description:
Sets the mode to select the fixed speed setpoint.
Value:
1:
Direct
2:
Binary
Note
For p1016 = 1:
In this mode, the setpoint is entered via the fixed speed setpoints p1001 ... p1004.
Up to 16 different setpoints are obtained by adding the individual fixed speed setpoints.
For p1016 = 2:
In this mode, the setpoint is entered via the fixed speed setpoints p1001 ... p1015.
Parameters
7.2 Parameter list
SINAMICS G120X converter
612
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......