p1098[0...n]
CI: Skip speed scaling / n_skip scal
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: PERCENT
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3050
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for scaling the skip speeds.
Dependency:
See also: p1091, p1092, p1093, p1094
r1099.0
CO/BO: Skip band status word / Skip band ZSW
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the skip bands.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
r1170 within the skip band
Yes
No
3050
Dependency:
See also: r1170
Note
For bit 00:
With the bit set, the setpoint speed is within the skip band after the ramp-function generator (r1170).
The signal can be used to switch over the drive data set (DDS).
p1101[0...n]
Skip speed bandwidth / n_skip bandwidth
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3050
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Sets the bandwidth for the skip speeds/velocities 1 to 4.
Dependency:
See also: p1091, p1092, p1093, p1094
Note
The setpoint (reference) speeds are skipped (suppressed) in the range of the skip speed +/-p1101.
Steady-state operation is not possible in the skipped (suppressed) speed range. The skip (suppression) range is
skipped.
Example:
p1091 = 600 and p1101 = 20
--> setpoint speeds between 580 and 620 [rpm] are skipped.
For the skip bandwidths, the following hysteresis behavior applies:
For a setpoint speed coming from below, the following applies:
r1170 < 580 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 580 [rpm]
For a setpoint speed coming from above, the following applies:
r1170 > 620 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 620 [rpm]
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
629
Содержание SINAMICS G120X