p1030[0...n]
Motorized potentiometer configuration / Mop configuration
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3020
Min:
-
Max:
-
Factory setting:
0000 0110 bin
Description:
Sets the configuration for the motorized potentiometer.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Data save active
Yes
No
-
01
Automatic mode ramp-function generator active
Yes
No
-
02
Initial rounding-off active
Yes
No
-
03
Save in NVRAM active
Yes
No
-
04
Ramp-function generator always active
Yes
No
-
Note
For bit 00:
0: The setpoint for the motorized potentiometer is not saved and after ON is entered using p1040.
1: The setpoint for the motorized potentiometer is saved after OFF and after ON set to the saved value. In order to save
in a non-volatile fashion, bit 03 should be set to 1.
For bit 01:
0: Without ramp-function generator in the automatic mode (ramp-up/ramp-down time = 0).
1: With ramp-function generator in the automatic mode.
For manual operation (0 signal via BI: p1041), the ramp-function generator is always active.
For bit 02:
0: Without initial rounding-off
1: With initial rounding-off. The selected ramp-up/down time is correspondingly exceeded. The initial rounding-off is a
sensitive way of specifying small changes (progressive reaction when keys are pressed).
The jerk for the initial rounding-off is independent of the ramp-up time and only depends on the selected maximum
speed (p1082). It is calculated as follows:
r = 0.01 % * p1082 [1/s] / 0.13^2 [s^2]
The jerk acts up until the maximum acceleration is reached (a_max = p1082 [1/s] / p1047 [s]), and then the drive
continues to run linearly with a constant rate of acceleration. The higher the maximum acceleration (the lower that
p1047 is), the longer the ramp-up time increases with respect to the set ramp-up time.
For bit 03:
0: Non-volatile data save deactivated.
1: The setpoint for the motorized potentiometer is saved in a non-volatile fashion (for bit 00 = 1).
For bit 04:
When the bit is set, the ramp-function generator is computed independent of the pulse enable. The actual output value
of the motorized potentiometer is always in r1050.
p1035[0...n]
BI: Motorized potentiometer setpoint raise / Mop raise
G120X_DP,
G120X_PN
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2505, 3020
Min:
-
Max:
-
Factory setting:
[0] 2090.13
[1] 0
[2] 0
[3] 0
Description:
Sets the signal source to continually increase the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-up time (p1047) and the duration of the signal that is
present (BI: p1035).
Dependency:
See also: p1036
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
615
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......