Spare parts
Frame size
Article number
Terminal cover kit
FSD
6SL3200-0SM13-0AA0
FSE
6SL3200-0SM14-0AA0
FSF
6SL3200-0SM15-0AA0
FSG
6SL3200-0SM16-0AA0
External fan unit for the heat sink
FSA
6SL3200-0SF52-0AA0
FSB
6SL3200-0SF53-0AA0
FSC
6SL3200-0SF54-0AA0
FSD
6SL3200-0SF15-0AA0
FSE
6SL3200-0SF16-0AA0
FSF
6SL3200-0SF17-0AA0
FSG
6SL3200-0SF18-0AA0
FSH/FSJ
6SL3300-0SF01-0AA0
Internal fan unit
FSH/FSJ
6SL3200-0SF50-0AA0
Free programmable interface
FSH/FSJ
6SL3200-0SP05-0AA0
Power supply board
FSH/FSJ
6SL3200-0SP06-0AA0
Current sensor
FSH/FSJ
6SL3200-0SE01-0AA0
FSJ
6SL3200-0SE02-0AA0
10.2.3
Fan units
The average service life of the fan is 40,000 hours. In practice, however, the service life may
deviate from this value. Especially a dusty environment can block up the fan. The defective fan
must be replaced timely to ensure that the converter is ready for operation.
When must the fan unit be replaced?
A defective fan in operation results in an overtemperature condition of the converter. For
example, the following messages indicate that the fan unit is defective:
● A05002 (air intake overtemperature)
● A05004 (rectifier overtemperature)
● F30004 (heat sink overtemperature)
Corrective maintenance
10.2 Replacing spare parts
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
1055
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......