p11185
Free tec_ctrl 1 integral time / Ftec1 Tn
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0.000 [s]
Max:
10000.000 [s]
Factory setting:
30.000 [s]
Description:
Sets the integral time (I component, integrating time constant) of the free technology controller 1.
Note
Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
p11191
CO: Free tec_ctrl 1 limit maximum / Ftec1 lim max
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the maximum limit of the free technology controller 1.
Dependency:
See also: p11192
Note
The maximum limit must always be greater than the minimum limit (p11191 > p11192).
p11192
CO: Free tec_ctrl 1 limit minimum / Ftec1 lim min
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
0.00 [%]
Description:
Sets the minimum limit of the free technology controller 1.
Dependency:
See also: p11191
Note
The maximum limit must always be greater than the minimum limit (p11191 > p11192).
p11193
Free tec_ctrl 1 limit ramp-up/ramp-down time / Ftec1 lim r-u/r-dn
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7030
Min:
0.00 [s]
Max:
100.00 [s]
Factory setting:
1.00 [s]
Description:
Sets the ramp-up and ramp-down time for the maximum and minimum limit (p11191, p11192) of the free technology
controller 1.
Dependency:
See also: p11191, p11192
Note
The ramp-up/ramp-down times are referred to 100%.
Parameters
7.2 Parameter list
SINAMICS G120X converter
906
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......