Note
For p29522=0:
Motor selection for switching-in/switching-out follows a fixed sequence and is dependent on the multi-pump control
configuratin(p29521).
For p29522=1:
Motor selection for switching-in/switching-out is derived from the operating hours counter p29530.When switching-in,
the motor with the least operating hours is connected.When switching-out,the motor with the most operating hours is
disconnected.
p29523
Multi-pump control switch-in threshold / Mpc sw_in thr
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: 9_1
Unit selection: p0595
Function diagram: -
Min:
0.0 [%]
Max:
200.0 [%]
Factory setting:
20.0 [%]
Description:
Threshold value for the delayed switching-in or switching-out of motors.
Motor switching-in is activated if the maximum speed is reached and the wait time in p29524 has expired.
Dependency:
refer to P29524
p29524
Multi-pump control switch-in delay / Mpc_ctrl t_in_del
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [s]
Max:
650 [s]
Factory setting:
30 [s]
Description:
Additional delay time for staging motors after the system deviation of the technology controller has exceeded the
threshold value p29523 and the motor has reached the maximum speed.
Dependency:
refer to P29523
Note
If the deviation at the technology controller input exceeds the overcontrol threshold p29526, the delay time is bypassed.
p29525
Multi-pump control switch-out delay / Mpc sw_out del
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [s]
Max:
650 [s]
Factory setting:
30 [s]
Description:
Additional delay time for switch-out motor after the system deviation of the technology controller has exceeded the
threshold p29523 and the motor has reached the speed threshold p1080+P29528.
Dependency:
Refer to P29523,P29526
Note
If the deviation at the technology controller input exceeds the overcontrol threshold p29526, the delay time is bypassed.
If the hibernation mode is active, ensure that p2391 is longer than p29525 to avoid false operation of hibernation.
p29526
Multi-pump control overcontrol threshold / Mpc overctrl thr
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: 9_1
Unit selection: p0595
Function diagram: -
Min:
0.0 [%]
Max:
200.0 [%]
Factory setting:
25.0 [%]
Parameters
7.2 Parameter list
SINAMICS G120X converter
916
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......