Example: r0002 read acyclically
Table 6-56
Write parameter request: Reading the parameter value of r0002 from slave number 17
Value
Byte
Description
11 h
0
Slave address
10 h
0258 h
0007 h
0E h
0001 h
2F0A h
8001 h
0101 h
1001 h
0002 h
0000 h
1
2,3
4,5
6
7,8
9,10
11,12
13,14
15,16
17,18
19,20
Function code (write multiple)
Register start address
Number of registers to be read (40601 … 40607)
Number of data bytes (7 registers, each 2 bytes = 14 bytes)
40601: DS47 Control = 1 (activate request)
40602: Function 2F h (47), request length 10 bytes (0A h)
40603: Request reference = 80 h, request identifier = 1 h
40604: DO-Id = 1, number of parameters = 1
40605: Attribute, number of elements = 1
40606: Parameter number = 2
40607: Subindex = 0
xx h
xx h
21
22
CRC "Low"
CRC "High"
Table 6-57
Start parameter request: Reading the parameter value of r0002 from slave number 17
Value
Byte
Description
11 h
0
Slave address
03 h
0258 h
0007 h
0010 h
1
2,3
4,5
6,7
Function code (read)
Register start address
Number of registers to be read (40601 … 40607)
Number of registers
xx h
xx h
8
9
CRC "Low"
CRC "High"
Table 6-58
Response for successful read operation
Value
Byte
Description
11 h
0
Slave address
03 h
20 h
0002 h
2F08 h
8001 h
0101 h
0301 h
001F h
1
2
3,4
5,6
7,8
9,10
11,12
13,14
Function code (read)
Number of following data bytes (20 h: 32 bytes corresponds to 16 registers)
40601: DS47 Control = 2 (the request was executed)
40602: Function code 2F h (47), response lengths 8 bytes
40603: Request reference mirrored = 80 h,
response identifier = 1 (request parameter)
40604: DO-ID = 1, number of parameters = 1
40605: Format, number of elements = 1
40606: Parameter value = 1F h (31)
xx h
xx h
15
16
CRC "Low"
CRC "High"
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
257
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......