Instance
ID
Object name Description
Possible values
Text ac‐
tive
Text in‐
active
Ac‐
cess
type
1)
Parameter
BV4
MANUAL /
AUTO ACT
Source of Manual/Auto converter
control
AUTO / MAN‐
UAL
AUTO
LOCAL R
r0052.9
BV6
1)
MAINT REQ Maintenance required
MAINT/OK
MAINT OK
R
reserved
BV7
CTL OVER‐
RIDE ACT
Control of the converter from the
BACnet override control via BV93
The "Manual" mode of the operator
panel has a higher priority than the
BACnet override control.
ON/OFF
0
1
R
r2032[10]
BV8
AT SET-
POINT
Setpoint reached
YES / NO
YES
NO
R
r0052.8
BV9
AT MAX
FREQ
Maximum speed reached
YES / NO
YES
NO
R
r0052.10
BV10
DRIVE
READY
Converter ready
YES / NO
YES
NO
R
r0052.1
BV15
RUN COM
ACT
Status of the ON command, regard‐
less of the source
YES / NO
0
1
R
r2032[0]
BV16
HIB MOD
ACT
Energy saving mode is active
ON/OFF
0
1
R
r2399[1]
BV17
ESM MOD
Essential service mode is active
ON/OFF
0
1
R
r3889[0]
BV20
RUN / STOP
CMD
ON command for the converter
(when controlling via BACnet)
RUN / STOP
0
1
C
r0054.0
BV21
FWD / REV
CMD
Reverse direction of rotation (when
controlling via BACnet)
REV / FWD
0
1
C
r0054.11
BV22
FAULT RE‐
SET
Acknowledge fault (when controlling
via BACnet)
RESET / NO
0
1
C
r0054.7
BV24
CDS
Changeover drive control
Local / Remote
YES
NO
C
r0054.15
BV26
RUN ENA
CMD
Enable converter operation
ENA‐
BLED
DISA‐
BLED
C
r0054.3
BV27
OFF2
Status OFF2
RUN / STOP
0
1
C
r0054.1
BV28
OFF3
Status OFF3
BV28 sets the r0054.4, r0054.5, and
r0054.6 bits
RUN / STOP
0
1
C
r0054.2
BV50
ENABLE PID Enable technology controller
ENABLED / DIS‐
ABLED
ENA‐
BLED
DISA‐
BLED
C
p2200
BV51
ENABLE
PID 0
Enable technology controller 0
ENABLED / DIS‐
ABLED
ENA‐
BLED
DISA‐
BLED
C
p11000
BV52
ENABLE
PID 1
Enable technology controller 1
ENABLED / DIS‐
ABLED
ENA‐
BLED
DISA‐
BLED
C
p11100
BV53
ENABLE
PID 2
Enable technology controller 2
ENABLED / DIS‐
ABLED
ENA‐
BLED
DISA‐
BLED
C
p11200
BV90
LOCAL
LOCK
Use MANUAL (operator panel) to
lock converter control
LOCK
UN‐
LOCK
C
p0806
BV91
2)
LOCK PAN‐
EL
Interlocking for operator panel and
parameter changes
LOCK/UNLO
0
1
W
reserved
BV93
CTL OVER‐
RIDE CMD
Converter control using BACnet
override control
ON/OFF
0
1
C
r0054.10
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
283
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......