p3380
Forming activation/duration / Form act/duration
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.0 [h]
Max:
10.0 [h]
Factory setting:
0.0 [h]
Description:
Setting to activate the "DC link capacitor forming" function.
This value also defines the forming duration.
The function is deactivated with p3380 = 0.
Recommendation:
Recommended forming duration depending on the storage time:
1 - 2 years: p3380 = 1 hour
2 - 3 years: p3380 = 2 hours
>3 years: p3380 = 8 hours
Dependency:
The "DC link capacitor forming" function can only be executed when commissioning the power unit (p0010 = 2). The
function is automatically deactivated (p3380 = 0) once commissioning has been exited (p0010 = 0).
Procedure when forming:
1. Activate power unit commissioning (p0010 = 2).
2. Activate forming (p3380 > 0, value, see recommendation).
3. Switch on the drive unit (p0840 = 0/1 signal).
4. Wait for forming to be completed (r3381 = 0).
5. Exit power unit commissioning (p0010 = 0).
See also: r3381, r3382
See also: F07390, A07391
NOTICE
If drive units are not commissioned within 2 years after their original manufacture, then the DC link capacitors must be
reformed before use. If this is not done, then the units could be damaged in operation.
Note
The "DC link capacitor forming" function can only be activated online in the drive unit.
If switched off while forming is active, the remaining time (r3381) is lost, and forming must be repeated for the full
forming time. If the forming duration is changed, then forming starts again from the beginning.
r3381
Forming remaining time / Forming t_remain
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [h]
Max:
- [h]
Factory setting:
- [h]
Description:
Displays the remaining time after activating the "DC link capacitor forming" function.
Dependency:
See also: p3380, r3382
r3382
Forming status word / Forming ZSW
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status word of the "DC link capacitor forming" function.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Forming activated
Yes
No
-
01
Forming active
Yes
No
-
Parameters
7.2 Parameter list
SINAMICS G120X converter
840
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......