Description:
Control and feedback signals of the bypass switch.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Command switch motor - power unit
Close
Open
-
01
Command switch motor - line supply
Close
Open
-
05
Feedback signal switch motor - power unit
Closed
Opened
-
06
Feedback signal switch motor - line supply
Closed
Opened
-
07
Bypass command (from p1266)
Yes
No
-
10
Bypass in process sequence
Yes
No
-
11
Bypass enabled
Yes
No
-
Dependency:
The "Bypass" function is only available for induction motors.
Note
Control bits 0 and 1 should be interconnected to the signal outputs via which the switches in the motor feeder cables
should be controlled. These should be selected/dimensioned for switching under load.
p1262[0...n]
Bypass dead time / Bypass t_dead
Access level: 2
Calculated: CALC_MOD_REG Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.000 [s]
Max:
20.000 [s]
Factory setting:
1.000 [s]
Description:
Sets the dead time for non-synchronized bypass.
Dependency:
The "Bypass" function is only available for induction motors.
Note
This parameter is used to define the changeover time of the contactors. It should not be shorter than the de-magnetizing
time of the motor (p0347).
The total changeover time for the bypass is based on the total of p1262 plus the OFF time for the relevant switch
(p1274[x]).
p1263
Debypass delay time / Debypass t_del
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.000 [s]
Max:
300.000 [s]
Factory setting:
1.000 [s]
Description:
Sets the delay time to switch back to converter operation for a non-synchronized bypass.
Dependency:
The "Bypass" function is only available for induction motors.
p1264
Bypass delay time / Bypass t_del
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.000 [s]
Max:
300.000 [s]
Factory setting:
1.000 [s]
Description:
Sets the delay time for switching to line operation for a non-synchronized bypass.
Dependency:
The "Bypass" function is only available for induction motors.
Parameters
7.2 Parameter list
SINAMICS G120X converter
660
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......