TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
4-73
Monday
, November 26, 2001 1:09 pm
4.
Press the button on the Safety Switch cable until the alarm ceases.
• If the Safety Switch is not pressed within 60 seconds, the test is
aborted and the window shown in Figure 4.45 appears.
• If the Safety Switch is released before the alarm ceases, the test is
aborted and the window shown in Figure 4.46 appears.
Figure 4.45 Test Abort Message – Switch Release
Figure 4.46 Test Abort Message – Switch Not Operated
The window shown in Figure 4.47 appears as the data is collected.