TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
A-123
Monday
, November 26, 2001 1:09 pm
D
Average Velocities (Figure A.145) as specified for
the trip operation are tabulated here. The close
position baseline cannot be clearly defined during
trip-free operation. Consequently, if close position
baseline is used to specify the Average Velocity
Zone in trip operation (for example, if the zone is
defined by distance-distance or distance-time), this
velocity is not tabulated for trip-free operation.
Figure A.145 Trip-Free Test Mechanical Motion – Average Velocities
MECHANICAL MOTION CHANNELS 1-3
TRIP OPERATION
| |
Specifications | Test results | Compare
| |
Average velocity in Open zone 2
Maximum 15.50 Ft/Sec | Ft/Sec |
Minimum 12.60 | VEL. 2 14.42 | Pass
Zone 2 Open to 6.250 in. | |
Average velocity in Close zone 2
Maximum 17.00 Ft/Sec | Ft/Sec |
Minimum 15.00 | VEL. 2 15.86 | Pass
Zone 2 6.250 in. to Close | |
D
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...