TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
A-73
Monday
, November 26, 2001 1:09 pm
Main Contact
Timing – Reclose
Parameters include:
Minimum
The minimum time from trip initiation to Main
Contact make
Maximum
The maximum time from trip initiation to Main
Contact make.
Figure A.85 shows how contact timing occurs on a module-by-module
level.
Module (A)
The maximum allowable difference in time
between the Trip initiation and the closing of the
two Main Contacts in any module.
Phase (B)
The maximum allowable difference in time
between the Trip initiation and the closing of any
two Main Contacts in any phase.
Breaker (C)
The maximum allowable difference in time
between the Trip initiation and the closing of any
two Main Contacts in a circuit breaker.
Figure A.85 Main Contact Timing – Reclose
Module #1
Module #1
Module #2
Module #1
Module #2
Module #2
#!
#2
#3
#4
#!
#2
#3
#4
Contact #1
Contact #2
Contact #3
Contact #4
Main Contact reopening time
C
0
A
0
C
0
20
40
60
80
Time (ms)
First Switch to Last Switch
B
A
0
B
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...