F
Average Velocity measured in the Zone specified
for a trip test (Figure A.150).
G
Average Velocity measured in the Zone specified
for a close test (Figure A.150).
Figure A.150 Average Velocity Characteristics for a Reclose Test
| |
Specifications | Test results | Compare
| |
Average velocity in Open zone 1
Maximum 15.50 Ft/Sec | Ft/Sec |
Minimum 12.60 | VEL. 2 13.66 | Pass
Zone 1 0.250 in. to 6.500 in. | |
Average velocity in Open zone 2
Maximum 15.50 Ft/Sec | Ft/Sec |
Minimum 12.60 | VEL. 2 14.58 | Pass
Zone 2 Open to 6.250 in. | |
Average velocity in Close zone 1
Maximum 17.00 Ft/Sec | Ft/Sec |
Minimum 15.00 | VEL. 2 ****** |
Zone 1 6.500 in. to 0.250 in. | |
Average velocity in Close zone 2
Maximum 17.00 Ft/Sec | Ft/Sec |
Minimum 15.00 | VEL. 2 16.97 | Pass
Zone 2 6.250 in. to Close | |
F
G
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...