Interruption in SF
6
A-14
72A-1898 Rev. A 11/01
Monday
, November 26, 2001 1:09 pm
Puffer-Type SF
6
Circuit Breakers
Figure A.13 shows the structure of a Puffer-Type SF
6
Circuit Breaker
(courtesy of Mitsubishi Electric). These circuit breakers are sometimes
called
single-pressure
or
impulse
-
type
circuit breakers. Circuit breakers
of this type are applied in 765 kV range.
Figure A.13 Puffer Type SF
6
Circuit Breaker Operation
The SF
6
gas in the cylinder is compressed by the downward movement of
the cylinder and is forced into the nozzle area where the arc is drawn
between the stationary arc contact and the moving arc contact. The
nozzle concentrates the gas flow to the area of the arc, resulting in very
effective arc extinction.
Closed Position
Interrupting Principle
Arc
Moving Arcing Contact
Puffer Cylinder
Piston
Fixed Main Contact
Fixed Arcing Contact
Nozzle
Moving Main Contact
Contact
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...