TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
3-17
Monday
, November 26, 2001 1:09 pm
OCB/Motion
The OCB portion of this module measures main and resistor switch
contact operation timing when a Dead Tank or candlestick circuit
breaker is closed or opened. Trip and Close pre-insertion resistor value
ranges are configurable, and this configuration applies to all three
contacts of the OCB connector. Contact status information is available
for each individual contact. An option is available (Doble P/N T9120)
that measures the Ohmic value of pre-insertion resistors.
The motion portion of this module records the motion of the circuit
breaker contacts through a digital rotary or linear transducer attached to
the operating mechanism. Possible configurations include three or six
motion channels.
Data can be presented in English or Metric units. The TRXField software
has the ability to set two user-defined zones for the measurement of
velocities and to set a range of expected speeds that should occur in
those zones. Additionally, to accommodate the need for indirect
measurements on some transducers, TRXField includes a Transfer
Function. The Transfer Function performs a linear scaling calculation
using two user-entered values that transform a measurement taken at a
transducer to one equal to a contact’s travel.
The OCB/Motion module, if used, must reside in Location 1. Its
configuration is discussed in ”Configuring the OCB/Motion Module”
on page 4-45.
Figure 3.14 on page 3-18 maps the relationship between those
parameters set only on the Test Plan tab and the Virtual Front Panel
connectors they effect.
N
OTE
OCB and Motion functions are independent, but are packaged
individually or in any combination to meet the application
requirements.
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...