TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
A-95
Monday
, November 26, 2001 1:09 pm
Distance – Contact Close
The Circuit Breaker Average Velocity is calculated
for the period between the moment when the Main
Contacts make and the time specified before the
make (Figure A.114).
Figure A.114 Contact Closed Time – Contact Close Oil Circuit Breaker
Final Closed Position
(end of test)
Oil Circuit Breaker
Zone 1
From
Distance
Starting Open Position
(start of test)
#1
#2
#3
Phase where motion
channel is activated and
Transducer is installed.