TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
2-17
Monday
, November 26, 2001 1:09 pm
O-C-O
Figure 2.12 gives a simplified representation of the test waveform
generated for the O-C-O test.
Figure 2.12 O-C-O Command Pulse
Command
Parameters
Trip Command
This time setting determines the duration of the first
Trip Pulse sent to operate the trip circuit of the
circuit breaker.
Close Command, Delay 1 and Delay 2
These parameters determine when the Close Pulse
is initiated:
Standing
Initiates .5 cycles (8.3 ms at 60 Hz) after the Trip
Pulse. The second Trip Pulse occurs – measured
from the start of the Close Pulse – after the time
specified in
Delay 2
.
Delay
Initiates a Close after the time entered in
Delay 1
that appears when
Delay
is selected.
Delay 2
also
appears, which determines when the second Trip
Pulse is sent. Both delays are measured from the
start of the Close Pulse.
Contact 1 Make
Standing and Delay
Trip Command
Close Command
Trip Command
Close Command
Delay 1
Delay 2
Delay
Contact
Make
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...