TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
4-63
Monday
, November 26, 2001 1:09 pm
N
OTE
When a test with a length greater than 5 minutes is completed, the
Safety Bypass Plug must be used. The TDR9000 will not commence a
test without it.
K
A Signal Viewer functionality button that is used to
restore both the Trip Command or Close Command
graph once they have been closed. Right-click
anywhere on the
Parameters
window to access
Signal Viewer help or the Signal Viewing
Properties window.
Table 4.6 Recording Lengths and Sampling Rate
Recording Length
Sampling Rate
500 ms
10 kHz
1600 ms
10 kHz
10 s
1 kHz
30 s
500 Hz
1 min
200 Hz
5 min
50 Hz
20 min
10 Hz