TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
A-35
Monday
, November 26, 2001 1:09 pm
Device Timing
Parameters
These parameters apply to the tests overall. Restrictions are discussed
individually.
Delay Length:
Delay Length and Delay 1 Length/Delay 2 Length
Delay Length is the length of time after the
inception of running a test before the test
condition, for example a trip pulse, is
implemented.
Delay 1 Length sets the time for a first test
condition to be implemented.
Delay 2 Length sets the time, for those tests where
it is applicable, such as an O-C-O test, for a second
test condition to be applied.
Each of these choices activate the Trip, Close, and
Delay 1 and 2 fields as listed in Table A.1.
Table A.1 Delay Command Parameters
Test Type
Command Parameters
Reclose (O-C)
Standing
Trip Command
Delay
Trip Command
Delay 1 (Close Command)
Trip Free (C-O)
Standing
Close Command
Delay
Close Command
Delay 1 (Trip Command)
Contact 1 Make
Close Command
O-C-O
Standing
Trip Command
Close Command
Delay 2 (Trip Command)
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...