Test Plan Items
A-92
72A-1898 Rev. A 11/01
Monday
, November 26, 2001 1:09 pm
Velocity Open
Zone 1 and 2
Velocity Open Zone 1 is comprised of Open and Close parameters listed
above. Zone 2 is similar to Zone 1 and is totally independent of Zone 1
(Figure A.108 on page A-91).
Distance – Distance The Circuit Breaker Average Velocity is calculated
between the two distances specified. Distances are
relative to the final closed position (0.000 in/mm)
of the circuit breaker (Figure A.116 on page A-97).
In Figure A.109, the end distance (
T0
) must be less
than the start distance (
FROM
).
Figure A.109 Contact Close Distance – Distance
Distance – Time
The Circuit Breaker Average Velocity is calculated
between the distance specified and a time after the
circuit breaker mechanism passes the first specified
point. Distance is relative to the final closed
position (0.000 in/mm) of the circuit breaker
(Figure A.110).
Figure A.110 Contact Closed Distance – Time
Starting Open Position
(start of test)
From
Distance
To
Distance
Final
Closed Position
Starting Open Position
(start of test)
From
Distance
To
Distance
Final
Closed Position
Zone 1
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...