Reclose Test Tabulation
A-124
72A-1898 Rev. A 11/01
Monday
, November 26, 2001 1:09 pm
Reclose Test Tabulation
This section discusses the characteristics of the Reclose test results.
Figure A.146 shows the top portion of the Breaker test report for a
Reclose test. Refer to ”Reclose Parameters (O-C)” on page A-45 for
more information on these parameters.
Figure A.146 Dead Tank Breaker Reclose Test Report – Header
A
Dead Time
This is the time when at least one Main Contact
within a phase is open during the reclose operation
(Figure A.147).
Figure A.147 Reclose Dead Time within a Phase
Contact #1
Contact #2
First to open
Last to close
Dead Time
0