TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
A-49
Monday
, November 26, 2001 1:09 pm
The Instrument does not impose any special restrictions on Delay 1
Length, however, the following formula is useful:
Delay 1 Length < 55 ms + Trip Pulse
The default value is:
55 ms
The Delay 2 Length can be calculated as follows:
Delay 2 Length > 55 ms + (Trip pulse – Delay 1 Length)
The default value is:
Delay 2 Length = 55 ms + (66.6 ms – 55 ms) = 66.6 ms
Figure A.59 shows how the O-C-O Delay works.
Figure A.59 Reclose Trip Delay Operation
Contact 1 Make
A trip command of a specified duration is applied to the circuit breaker at
time zero (Figure A.60). A close command of a specified duration is
applied to the circuit breaker delayed by a specified time (delay) after the
initiation of the trip command. The second trip command is initiated
when electrical closure is first detected on the Main Contact channel #1
(usually connected to contact #1 in Phase A) and is left on for the
duration of the test.
Figure A.60 O-C-O Contact 1 Make
delay2
delay 1
Trip Command
Close Command
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...