Test Plan Items
A-96
72A-1898 Rev. A 11/01
Monday
, November 26, 2001 1:09 pm
For the EHV Circuit Breaker, the Instrument uses
the data for Main Contact 1 from the phase of the
active motion channel (Figure A.115).
Figure A.115 Contact Closed Time – Contact Close EHV Circuit Breaker
Module #1
Module #1
Module #1
Module #2
Module #2
#!
#2
#3
#4
#!
#2
#3
#4
Contact #1
Contact #2
Contact #3
Contact #4
0A
0C
0B
Starting Open Position
Zone 1
To Contact Close
From
Motion channel is activated
and the Transducer is installed
on Phase C.
Distance
Module #2
Final Close Position
(end of test)
EHV Circuit Breaker or Circuit Switcher