TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
2-15
Monday
, November 26, 2001 1:09 pm
Reclose (O-C)
Figure 2.10 is a simplified representation of the test waveform generated
for the Reclose test.
Figure 2.10 Reclose Command Pulse
Command
Parameters
Trip Pulse
This time setting determines the duration of the
Trip Pulse sent to operate the trip circuit of the
circuit breaker.
Close Pulse
This pulse, initiated after the Trip Pulse, operates
the close circuit and performs the Reclose function.
Reclose and Delay
These parameters determine when the Close Pulse
is initiated:
Standing
Initiates a Close .5 cycles (8.3 ms at 60 Hz) after
the test starts. This occurs when
Standing
is
selected in the
Reclose
field.
Delay
Initiates a Close after the time entered in the
Delay
Length
field that appears when
Delay
is selected in
the
Reclose
field.
Recording Length
This setting determines the recording length and
implicitly sets the sampling rate at which the
recording is performed.
66 msecs
Trip Command
Close Command
Delay
On
Off
On
Off
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...