Test Plan Items
A-74
72A-1898 Rev. A 11/01
Monday
, November 26, 2001 1:09 pm
Main Contact
Timing: Trip-Free
Dwell – Reclose
Dead
Trip-Free Dwell parameters include:
Trip-Free Dwell min The minimum time the Main Contacts may be
CLOSED during a Trip-Free test.
Trip-Free Dwell max The maximum time the Main Contacts may be
CLOSED during a Trip-Free test.
Figure A.86 shows the Trip-Free Dwell Time.
:
Figure A.86 Trip-Free Dwell Time
Reclose-Dead Time parameters include:
Reclose Dead min
The minimum time the Main Contacts are OPEN
during a Reclose test.
Reclose Dead max
The maximum time the Main Contacts are OPEN
during a Reclose test.
Figure A.87 shows the Reclose Dead Time.
Figure A.87 Reclose Dead Time
Dwell Time
Reclose Dead Time
Close
Open