Parameter list
Parameters
1-95
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the input terminal to connect probe 1.
Values:
0:
No probe
1:
DI/DO 9 (X122.8)
2:
DI/DO 10 (X122.10)
3:
DI/DO 11 (X122.11)
4:
DI/DO 13 (X132.8)
5:
DI/DO 14 (X132.10)
6:
DI/DO 15 (X132.11)
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency:
Refer to: p0489, p0728
Note:
DI/DO: Bidirectional digital input/output
The terminal must be set as input (p0728).
Refer to the encoder interface for PROFIdrive.
Description:
Sets the input terminal to connect probe 2.
Values:
0:
No probe
1:
DI/DO 9 (X122.8)
2:
DI/DO 10 (X122.10)
3:
DI/DO 11 (X122.11)
4:
DI/DO 13 (X132.8)
5:
DI/DO 14 (X132.10)
6:
DI/DO 15 (X132.11)
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency:
Refer to: p0488, p0728
Note:
DI/DO: Bidirectional digital input/output
The terminal must be set as input (p0728).
Refer to the encoder interface for PROFIdrive.
Description:
Sets the behavior for the ENCODER fault response (motor encoder).
This means, for example, if an encoder fault occurs, sensorless operation can be automatically selected with a
shutdown behavior that can be selected.
p0488[0...2]
Measuring probe 1 input terminal / Meas probe 1 input
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Data set:
-
Function diagram:
4740
P-Group:
Encoder
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 6
0
p0489[0...2]
Measuring probe 2 input terminal / Meas probe 2 input
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Data set:
-
Function diagram:
4740
P-Group:
Encoder
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 6
0
p0491
Motor encoder fault response: ENCODER / Fault resp ENCODER
VECTOR
Can be changed:
T
Access level:
3
Data type:
Integer16
Data set:
-
Function diagram:
-
P-Group:
Encoder
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 3
0