Faults and Alarms
List of faults and alarms
3-516
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
A01035 (F)
ACX: Run-up from the back-up files
Reaction:
NONE
Acknowledge:
NONE
Cause:
When the control unit ran-up no complete data set from the parameter save files was found. The last time that the
parameterization was saved, it was not completely carried-out. Instead, a backup data set or file is downloaded.
Alarm value (r2124, hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
If you saved the project in STARTER, carry-out a new download for your project and save using the function "Copy
RAM to ROM" or with p0977 = 1 so that all of the parameter files are again completely written into the CompactFlash
Card.
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowledge
upon F:
IMMEDIATELY
F01036 (A)
ACX: Parameter back-up file missing
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
When downloading the device parameterization, a file associated with a drive object cannot be found. Neither a
PSxxxyyy.ACX, a PSxxxyyy.NEW nor a PSxxxyyy.BAK exists on the CompactFlash Card for this drive object.
Fault value (r0949, hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
If you have saved your project data using STARTER, carry-out a new download for your project. Save using the func-
tion "Copy RAM to ROM" or with p0977 = 1 so that all of the parameter files are again completely written into the
CompactFlash Card.
If you have not saved the project data, then the system must be again commissioned for the first time.
Reaction upon A:
NONE
Acknowledge
upon A:
NONE
F01037 (A)
ACX: Re-naming parameter file not successful
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The re-naming after saving a parameter-save file on the CompactFlash Card was unsuccessful.
One of the files to be re-named had the "read only" attribute. The parameter-save files are saved on the Compact-
Flash Card in the directory \USER\SINAMICS\DATA.
It is possible that the CompactFlash Card is defective.
Fault value (r0949, hexadecimal):
The least-significant byte includes the drive object number (yyy in the file names PSxxxyyy.* or CAxxxyyy.* or
CCxxxyyy.*).
Special cases: yyy = 0 --> consistency save file PSxxx000.*, yyy = 99 --> PROFIBUS parameter file PSxxx099.*
The next most significant byte includes the file number xxx.
The value for xxx depends on p0977 with which the save operation was started:
p0977 = 1, 10, 11, 12 --> xxx = 0, 10, 11, 12
The two most significant bytes are used for internal Siemens troubleshooting.
Remedy:
Check whether one of the files to be overwritten has the attribute "read only" and change this file attribute into "writ-
able". Check all of the files (PSxxxyyy.*, CCxxxyyy.*, CAxxxyyy.*) that belong to drive yyy designated in the fault
value.
Replace the CompactFlash Card.
Reaction upon A:
NONE
Acknowledge
upon A:
NONE
F01039 (A)
ACX: Writing into parameter file not successful.
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY