Parameters
Parameter list
1-148
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the skip speed/velocity 4.
Dependency:
Refer to: p1091, p1092, p1093, p1101
Description:
Sets the bandwidth for the skip speeds/velocities 1 to 4.
Dependency:
Refer to: p1091, p1092, p1093, p1094
Note:
The setpoint (reference) speeds are skipped (suppressed) in the range of the skip speed +/-p1101.
Steady-state operation is not possible in the skipped (suppressed) speed range. The skip (suppression) range is
skipped.
Example:
p1091 = 600 and p1101 = 20 --> setpoint speeds of between 580 and 620 [RPM] are skipped.
Description:
Sets the signal source to disable the negative direction.
Dependency:
Refer to: p1111
Description:
Sets the signal source to disable the positive direction.
Dependency:
Refer to: p1110
Description:
Displays the speed / velocity setpoint after the minimum limiting.
Dependency:
Refer to: p1091, p1092, p1093, p1094, p1101
p1094[0...n]
Skip speed 4 / Skip speed 4
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
3050
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
0.000 [1/min]
210000.000 [1/min]
0.000 [1/min]
p1101[0...n]
Skip speed bandwidth / Skip_n bandwidth
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
3050
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
0.000 [1/min]
210000.000 [1/min]
0.000 [1/min]
p1110[0...n]
BI: Inhibit negative direction / Inhibit negative
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2505
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
p1111[0...n]
BI: Inhibit positive direction / Inhibit positive
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2505
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
r1112
CO: Speed setpoint after minimum limiting / n_set n. min_lim
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
3050
P-Group:
Setpoints
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
- [1/min]
- [1/min]
- [1/min]