Parameter list
Parameters
1-187
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the P gain of the speed/velocity controller for the upper adaptation speed range/velocity range (> p1465). The
entry is made referred to the P gain for the lower adaptation speed range/velocity range of the speed/velocity con-
troller (% referred to p1460).
Dependency:
Refer to: p1460, p1464, p1465
Note:
SERVO:
When automatically calculating the speed controller, only the motor moment of inertia is taken into account (p0341).
For higher load moments of inertia (p0342 > 1 or p1498 > 0) we recommend that the speed controller gain is
checked.
Description:
Sets the integration action time of the speed/velocity controller before the adaptation speed range/velocity range (0
... p1464). This value corresponds to the basic setting of the integral action time of the speed/velocity controller
without adaptation (p1461 = 100 %).
Dependency:
Refer to: p1463, p1464, p1465
Description:
Sets the integral action time of the speed/velocity controller after the adaptation speed range/velocity range (>
p1465). The entry is made referred to the integral action time for the lower adaptation speed range/velocity range of
the speed/velocity controller (% referred to p1462).
Dependency:
Refer to: p1462, p1464, p1465
Description:
Sets the lower adaptation speed/velocity of the speed/velocity controller. No adaptation is effective below this
speed/velocity.
Dependency:
Refer to: p1460, p1461, p1462, p1463, p1465
p1461[0...n]
Speed controller P gain adaptation speed, upper / n_ctrl Kp n upper
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
5050,
6050
P-Group:
Control
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
0.000 [%]
200000.000 [%]
100.000 [%]
p1462[0...n]
Speed controller integral action time adaptation speed, lower / n_ctrl Tn n lower
VECTOR (n/M)
Can be changed:
U, T
Access level:
2
Data type:
Floating Point
Data set:
DDS
Function diagram:
5040,
5050, 6040, 6050
P-Group:
Control
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
0.00 [ms]
100000.00 [ms]
20.00 [ms]
p1463[0...n]
Speed controller integral action time adaptation speed, upper / n_ctrl Tn n upper
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
5050,
6050
P-Group:
Control
Units group:
PERCENT
Unit selection:
-
Min Max
Factory
setting
0.0 [%]
200000.0 [%]
100.0 [%]
p1464[0...n]
Speed controller adaptation speed, lower / n_ctrl n lower
VECTOR (n/M)
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
DDS
Function diagram:
5050,
6050
P-Group:
Control
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
0.00 [1/min]
210000.00 [1/min]
0.00 [1/min]