Parameter list
Parameters
1-125
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Displays or sets the PROFIBUS address for PROFIBUS interface X126 on the control unit. The address can be set
as follows:
1) Using the DIP power-up the control unit.
--> p0918 can then only be read and displays the selected address.
--> A change only becomes effective after a POWER ON.
2) Using p0918
--> only if all of the DIP switches - from S1 to S7 - are either set to ON or OFF.
--> a change becomes immediately effective
Note:
Permissible PROFIBUS addresses: 1 ... 126
Address 126 is intended for commissioning.
Every change of the DIP switch only becomes effective after a POWER ON.
Description:
Sets the send and receive telegram for PROFIBUS.
Either a standard telegram 1 according to PROFIdrive can be selected or a telegram can be freely configured.
Values:
1:
Standard telegram 1
999:
Free telegram configuration with BICO
Dependency:
Refer to: F01505, F01506
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again if a value of 999 was set.
Description:
Displays the operating mode.
1: Closed-loop speed controlled operation with ramp-function generator
3: Closed-loop speed controlled operation without ramp-function generator
p0918
PROFIBUS address / PROFIBUS address
CU
Can be changed:
T
Access level:
2
Data type:
Unsigned16
Data set:
-
Function diagram:
1520,
2410
P-Group:
Communication
Units group:
-
Unit selection:
-
Min Max
Factory
setting
1 126
126
p0922
PROFIBUS PZD telegram selection / PB PZD telegr_eval
VECTOR
Can be changed:
C2, T
Access level:
1
Data type:
Unsigned16
Data set:
-
Function diagram:
1520,
2420, 2460, 2470
P-Group:
Communication
Units group:
-
Unit selection:
-
Min Max
Factory
setting
1 999
999
r0930
PROFIBUS operating mode / PB operating mode
VECTOR
Can be changed:
-
Access level:
3
Data type:
Unsigned16
Data set:
-
Function diagram:
-
P-Group:
Setpoints
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-