Parameter list
Parameters
1-159
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Note:
The faults are automatically acknowledged after half of the waiting time has expired.
Description:
Sets the monitoring time of the automatic restart (AR).
Dependency:
Refer to: p1210, r1214
Cautiont:
A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Note:
The monitoring time starts when the faults are detected. If the automatic acknowledgements are not successful, the
monitoring time runs again. If, after the monitoring time has expired, the drive has still not successfully restarted
(the motor must have been magnetized), then fault F07320 is output.
The monitoring is de-activated with p1213 = 0. If p1213 is set lower than the sum of p1212 and the magnetization
time r346, then fault F07320 is generated at each restart.
Description:
Automatic restart (AR) status word.
Description:
Sets the holding brake configuration.
Values:
0:
No motor holding brake being used
1:
Motor holding brake acc. to sequential control
2:
Motor holding brake always open
3:
Motor holding braking can be parameterized via BICO just like the sequential control, brake connection
Dependency:
Refer to: p1216, p1217, p1226, p1227
p1213
Automatic restart, monitoring time line supply return / WEA t_mon line sup
VECTOR
Can be changed:
U, T
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Functions
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0.0 [s]
1999.0 [s]
0.0 [s]
r1214
CO/BO: Automatic restart, status / AR status
VECTOR
Can be changed:
-
Access level:
4
Data type:
Unsigned16
Data set:
-
Function diagram:
-
P-Group:
Functions
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
Initialization
No
Yes
-
01
Wait for alarm
No
Yes
-
02
Auto restart act.
No
Yes
-
04
Acknowledge alarms
No
Yes
-
05
Restart
No
Yes
-
06
Wait time running
No
Yes
-
07
Fault
No
Yes
-
12
Start count. bit 0
Off
On
-
13
Start count. bit 1
Off
On
-
14
Start count. bit 2
Off
On
-
15
Start count. bit 3
Off
On
-
p1215
Motor holding brake configuration / Brake config
VECTOR
Can be changed:
U, T
Access level:
2
Data type:
Integer16
Data set:
-
Function diagram:
2701
P-Group:
Functions
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 3
0