Parameter list
Parameters
1-71
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
Description:
Displays the motor rated torque/force.
Note:
For induction and reluctance motors, r0333 is calculated from p0307 and p0311.
For synchronous motors, r0333 is calculated from p0305, p0316, p0327 and p0328. The result can deviate from the
input in p0312. If p0316 = 0, then r0333 = p0312 is displayed.
Description:
Displays the torque/force constant of the synchronous motor used.
Dependency:
Refer to: p0316
Note:
This parameter is not used for induction motors (p0300 = 1xx).
For synchronous motors, parameter r0334 = p0316 is displayed. if p0316 = 0, r0334 is calculated from p0305 and
p0312.
Description:
Sets the motor cooling system used.
Values:
0:
Non-ventilated
1:
Forced-ventilated
2:
Water cooling
4:
Non-ventilated and internal fan
5:
Forced-ventilated and internal fan
6:
Water cooling and internal fan
Note:
The parameter influences the thermal 3-mass motor model.
1LA1 and 1LA8 motors are characterized by the fact that they have an internal rotor fan.
The parameter is automatically preset for motors from the motor list (p0301).
Description:
Displays the rated frequency of the motor.
For p0310 > 0, this value is displayed.
Dependency:
Refer to: p0311, p0314
r0333[0...n]
Rated motor torque / Mot M_rated
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
MDS
Function diagram:
-
P-Group:
Motor
Units group:
TORQUE
Unit selection:
-
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
r0334[0...n]
Motor-torque constant, actual / Mot kT act
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
MDS
Function diagram:
-
P-Group:
Motor
Units group:
TORQUE_PER_CURR
Unit selection:
-
Min Max
Factory
setting
- [Nm/A]
- [Nm/A]
- [Nm/A]
p0335[0...n]
Motor cooling type / Motor cooling type
VECTOR
Can be changed:
C2, T
Access level:
1
Data type:
Integer16
Data set:
MDS
Function diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 6
0
r0336[0...n]
Rated motor frequency (actual) / Mot f_rated act
VECTOR
Can be changed:
-
Access level:
3
Data type:
Floating Point
Data set:
MDS
Function diagram:
-
P-Group:
Motor
Units group:
FREQUENCY
Unit selection:
-
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]