Terminal Module 31 (TM31)
Function diagrams
2-499
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Picture 2-109 9566 – Analog input 0 (AI 0)
- 9566 -
Function diagram
8
7
6
5
4
3
2
1
fp_S01_9566_en.vsd
SINAMICS G
17.12.04
V02.02.00
Terminal module 31 (TM31) - analog input 0 (AI 0)
3
≠3
20 mA
T0
0...1000 ms
p4062[0] (100)
Threshold for
wire breakage detection
0.00...20.00 mA
p4061[0] (2.00)
r4055[0]
p4069[0]
(1)
Enable
p4066[0] (0)
(0)
p4067[0]
y = x if
|y - x| > p4068
otherwise y = y(old)
y
x
0 %
Smoothing
0.0...1000.0 ms
p4053[0] (0)
Window to suppress noise
0.0...100.0 %
p4068[0] (0.0)
1
0
<2>
For p4056 = 2, 3, 5 the units are mA.
For p4056 = 0, 4 the units are V.
S5.0
+/-20 mA
+/-10 V
X521.1
X521.2
Scaling
-20.000...20.000
p4057[0] (0.000)
-20.000...20.000
p4059[0] (10.000)
Act.ADC inpu
t
r4052[0]
p4097[0] (0)
Simulation mod
e
-20.000...20.000
p4098[0] (0.000)
-1000.00...1000.00 %
p4060[0] (100.00)
-1000.00...1000.00 %
p4058[0] (0.0)
[%]
1
0
xy
<2>
<2>
<2>
<2>
Hardware
smoothing
100 µs
A
D
+
-
AI 0
<1>
p4099[1] (4000.00 µs)
x
1
y
2
x
2
y
1
y
x
[%]
<9> Not implemented.
Reference quantities
p2000...r2004
y
x
2
x
1
DO: TM31
Voltage
V
V
Current
I S5.0
I S5.1
-1
0
1
0
1
Offset
-20.000...20.000
p4063[0] (0.000)
+
<2>
+
Analog inputs type
p4056[0] (4)
<3>
F03505 "wire
breakage"
×
%
100
x
x
2
1
•
[9568]
<1>
Differential input!
For ground-referred input signals, terminal X521.2 must be connected to the reference potential M.
Caution:
The voltage between an input (X521.1 or X521.2) and ground may not exceed 35 V. When the load resistor is switched-in (S5.1 clo
sed), the
voltage between the input terminals may not exceed 15 V.
<3>
p4056
= 0: 0 V ... +10 V
= 2: 0 mA ... +20 mA
= 3: 4 mA ... +20 mA with monitoring
= 4: -10 V ... +10 V
= 5: -20 mA ... +20 mA
4, 5
3
0, 2
4 mA
0
<2>