![Siemens SINAMICS G List Manual Download Page 59](http://html.mh-extra.com/html/siemens/sinamics-g/sinamics-g_list-manual_378180059.webp)
Parameter list
Parameters
1-59
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Displays the rated power module power for various load duty cycles.
Index:
[0] = Rating plate
[1] = Load duty cycle with high overload condition
[2] = Load duty cycle with slight overload condition
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency:
Refer to: p0205
Description:
Displays the rated line supply voltage of the power module.
r0208 = 400: 380 - 480 V +/-10 %
r0208 = 500: 500 -600 V +/-10 %
r0208 = 690: 660 - 690 V +/-10 %
The following applies for basic line modules:
r0208 = 690: 500 - 690 V +/-10 %
Description:
Displays the maximum output current of the power module.
Index:
[0] = Catalog
[1] = Load duty cycle with high overload condition
[2] = Load duty cycle with slight overload condition
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency:
Refer to: p0205
Description:
Sets the drive unit supply voltage.
AC/AC drive units: The RMS value of the phase-to-phase line supply voltage should be entered.
DC/AC drive units: The rated DC voltage of the supply busbars should be entered.
r0207[0...4]
Rated power module current / PM I_rated
VECTOR
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
8014
P-Group:
Drive converter
Units group:
CURRENT_AC_EFF
Unit selection:
-
Min Max
Factory
setting
- [Aeff]
- [Aeff]
- [Aeff]
r0208
Rated power module line supply voltage / PM U_rated
VECTOR
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Drive converter
Units group:
VOLTAGE_AC_EFF
Unit selection:
-
Min Max
Factory
setting
- [Veff]
- [Veff]
- [Veff]
r0209[0...4]
Power module, maximum current / PM I_max
VECTOR
Can be changed:
-
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
8950
P-Group:
Drive converter
Units group:
CURRENT_AC_EFF
Unit selection:
-
Min Max
Factory
setting
- [Aeff]
- [Aeff]
- [Aeff]
p0210
Drive unit line supply voltage / Supply voltage
VECTOR
Can be changed:
C2, T
Access level:
3
Data type:
Unsigned16
Data set:
-
Function diagram:
-
P-Group:
Drive converter
Units group:
VOLTAGE_DC
Unit selection:
-
Min Max
Factory
setting
1 [V]
1200 [V]
600 [V]