Parameters
Parameter list
1-64
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the run-on time of the fan after the power module is powered-down.
Description:
Selects the motor type or start command to download motor parameters from the integrated encoder evaluation
with p0300 = 10000.
The first digit of the parameter value (for p0300 < 10000) always defines the general motor type and corresponds to
the unlisted motor belonging to a motor list:
1 = Rotating induction motor
2 = Rotating synchronous motor (only for servo drives)
3 = Linear induction motor (reserved)
4 = Linear synchronous motor (reserved)
7 = SIEMOSYN motor (only for vector drives)
8 = Reluctance motor (only for vector drives)
The type information must be entered to filter motor-specific parameters and to optimize the operating characteris-
tics and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/AOP).
Values:
0:
No motor selected
1:
Induction motor (rotating)
2:
Synchronous motor (rotating, permanent-magnet)
7:
SIEMOSYN motor
8:
Reluctance motor
11:
1LA1 standard induction motor
15:
1LA5 standard induction motor
16:
1LA6 standard induction motor
17:
1LA7 standard induction motor
18:
1LA8 standard induction motor
102:
1PH2 induction motor
104:
1PH4 induction motor
107:
1PH7 induction motor
134:
1PM4 induction motor
136:
1PM6 induction motor
206:
1FT6 synchronous motor
236:
1FK6 synchronous motor
237:
1FK7 synchronous motor
10000: Motor with DRIVE-CLiQ
Dependency:
When the motor type is changed, the code number in p0301 may be reset to 0
Refer to: p0301
p0295
Fan run-on time / Fan run-on time
VECTOR
Can be changed:
U, T
Access level:
1
Data type:
Floating Point
Data set:
-
Function diagram:
-
P-Group:
Drive converter
Units group:
TIME
Unit selection:
-
Min Max
Factory
setting
0 [s]
600 [s]
0 [s]
p0300[0...n]
Mot type selection / Mot type selection
VECTOR
Can be changed:
C2
Access level:
2
Data type:
Integer16
Data set:
MDS
Function diagram:
6310
P-Group:
Motor
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 10000
0