Parameter list
Parameters
1-309
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the sampling time for the inputs and outputs of terminal module 31 (TM31).
Index:
[0] = Digital inputs/outputs
[1] = Analog inputs
[2] = Analog outputs
Dependency:
The parameter can only be modified for p0009 = 3, 29.
The sampling times can only be set as an integer multiple of the basic sampling time (p0110, p0111).
Refer to: p0009, p0110, p0111
Notice:
The sampling times entered in index 0 (digital inputs/outputs) and index 2 (analog outputs) must always be greater
than or equal to the sampling time in index 1 (analog inputs).
Note:
The modified sampling time is not effective until the drive unit is powered-up again.
Description:
Sets the temperature evaluation of terminal module 31 (TM31).
This means that the temperature sensor type is selected and the evaluation is switched-in.
Values:
0:
Evaluation disabled
1:
PTC thermistor
2:
KTY84
Note:
The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
Description:
Displays the actual resistance value of the temperature sensor connected at terminal module 31 (TM31).
Note:
The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
The maximum measurable resistance value is approx. 1700 Ohm.
p4099[0...2]
TM31 inputs/outputs, sampling time / TM31 I/O t_sample
TM31
Can be changed:
C1
Access level:
4
Data type:
Floating Point
Data set:
-
Function diagram:
9550
P-Group:
Commands
Units group:
TIME_M6
Unit selection:
-
Min Max
Factory
setting
0.00 [µs]
5000.00 [µs]
4000.00 [µs]
p4100
TM31 temperature evaluation, sensor type / TM31 temp sens_typ
TM31
Can be changed:
T
Access level:
1
Data type:
Integer16
Data set:
-
Function diagram:
9576,
9577
P-Group:
-
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 2
0
r4101
TM31 temperature evaluation, sensor resistance / TM31 temp R_sensor
TM31
Can be changed:
-
Access level:
3
Data type:
Unsigned16
Data set:
-
Function diagram:
9576,
9577
P-Group:
Terminals
Units group:
RESISTANCE
Unit selection:
-
Min Max
Factory
setting
- [Ohm]
- [Ohm]
- [Ohm]