![Siemens SINAMICS G List Manual Download Page 103](http://html.mh-extra.com/html/siemens/sinamics-g/sinamics-g_list-manual_378180103.webp)
Parameter list
Parameters
1-103
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Defines the ambient temperature of the motor to calculate the temperature model.
Note:
The parameters for stator and rotor resistance (p0350, p0354) refer to this temperature.
Description:
Defines the rated overtemperature of the stator core referred to the ambient temperature.
Dependency:
Refer to: p0625
Description:
Defines the rated overtemperature of the stator winding referred to the ambient temperature.
Dependency:
Refer to: p0625
Description:
Defines the rated overtemperature of the squirrel cage rotor referred to ambient temperature.
Dependency:
Refer to: p0625
Description:
Displays the ambient temperature of the motor temperature model.
p0625[0...n]
Motor ambient temperature / Mot T_ambient
VECTOR
Can be changed:
C2, U, T
Access level:
3
Data type:
Floating Point
Data set:
MDS
Function diagram:
8016
P-Group:
Motor
Units group:
TEMPERATURE
Unit selection:
-
Min Max
Factory
setting
-40 [°C]
80 [°C]
20 [°C]
p0626[0...n]
Motor overtemperature, stator core / Mot T_over core
VECTOR
Can be changed:
C2, U, T
Access level:
3
Data type:
Floating Point
Data set:
MDS
Function diagram:
8016
P-Group:
Motor
Units group:
TEMPERATURE_K
Unit selection:
-
Min Max
Factory
setting
20 [K]
200 [K]
50 [K]
p0627[0...n]
Motor overtemperature, stator winding / Mot T_over stator
VECTOR
Can be changed:
C2, U, T
Access level:
3
Data type:
Floating Point
Data set:
MDS
Function diagram:
8016
P-Group:
Motor
Units group:
TEMPERATURE_K
Unit selection:
-
Min Max
Factory
setting
20 [K]
200 [K]
80 [K]
p0628[0...n]
Rotor winding overtemperature / Mot T_over rotor
VECTOR
Can be changed:
C2, U, T
Access level:
3
Data type:
Floating Point
Data set:
MDS
Function diagram:
8016
P-Group:
Motor
Units group:
TEMPERATURE_K
Unit selection:
-
Min Max
Factory
setting
20 [K]
200 [K]
100 [K]
r0630[0...n]
Motor temperature model ambient temperature / MotTMod T_amb.
VECTOR
Can be changed:
-
Access level:
4
Data type:
Floating Point
Data set:
MDS
Function diagram:
8016
P-Group:
Motor
Units group:
TEMPERATURE
Unit selection:
-
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]