Parameter list
Parameters
1-123
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Note:
The state of the line contactor is monitored depending on signal BO: r0863.1.
For activated monitoring (BI: p0860 not equal to r0863.1), fault F07300 is then also output if the contactor is closed
before it is controlled using r0863.1.
Description:
Sets the monitoring time of the line contactor.
This time starts each time that the line contactor switches (r0863.1). If a feedback signal is not received from the
line contactor within the time, a message is output.
Dependency:
Refer to: p0860, r0863
Refer to: F07300
Note:
The monitoring function is disabled for the factory setting of p0860.
Description:
Sets the delay time for the control command of the power module and a line contactor, if used.
Note:
This means that it is possible to realize a shifted (delayed) pre-charging or power-on using a single ON command.
When the infeed units are active, before the line contactor is closed, an offset adjustment of the current measure-
ment is carried-out for a duration of 120 ms (p3491).
Description:
Displays the status and control words of the drive coupling.
Dependency:
Refer to: p0864
Note:
Bit 0 signals that the infeed is ready.
Bit 1 is used to control an external line contactor.
When transferring the operating message/signal via BO: r0863.0 allows several drives to start (run-up) staggered
over time when they are simultaneously powered-up.
To realize this, the following connections/interconnections are required:
Drive 1: BI: p0864 with BO: Interconnect r0863.0 of the infeed
Drive 2: BI: p0864 with BO: Interconnect r0863.0 from drive 1
Drive 3: BI: p0864 with BO: Interconnect r0863.0 from drive 2, etc.
The first drive only transfers the operating signal to the next drive after it has reached its ready condition.
p0861
Line contactor monitoring time / LineContact. t_mon
VECTOR
Can be changed:
T
Access level:
2
Data type:
Floating Point
Data set:
-
Function diagram:
8932
P-Group:
Commands
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
0 [ms]
5000 [ms]
100 [ms]
p0862
Power module ON delay / PM t_on
VECTOR
Can be changed:
T
Access level:
3
Data type:
Floating Point
Data set:
-
Function diagram:
2610,
8932
P-Group:
Commands
Units group:
TIME_M3
Unit selection:
-
Min Max
Factory
setting
0 [ms]
65000 [ms]
0 [ms]
r0863
CO/BO: Drive coupling status word/control word / CoupleZSW/STW
VECTOR
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Data set:
-
Function diagram:
1774,
2610, 8932, 8934
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
Infeed operation
No
Yes
-
01
Energize line contactor
No
Yes
-