![Siemens SINAMICS G List Manual Download Page 307](http://html.mh-extra.com/html/siemens/sinamics-g/sinamics-g_list-manual_378180307.webp)
Parameter list
Parameters
1-307
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Dependency:
The simulation of a digital input is selected using p4095.
Refer to: p4095
Note:
DI: Digital input
DI/DO: Bidirectional digital input/output
This parameter is not saved when data is backed-up (p0971, p0977).
Description:
Sets the simulation mode for the analog inputs of the terminal board 30 (TB30).
Values:
0:
Off
1:
On
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Dependency:
The setpoint for the input voltage is specified via p4098.
Refer to: p4098
Note:
AI: Analog input
This parameter is not saved when data is backed-up (p0971, p0977).
Description:
Sets the simulation mode for the analog inputs of terminal module 31 (TM31).
Values:
0:
No simulation mode for analog input x
1:
Simulation mode for analog input x
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The setpoint for the input voltage is specified via p4098.
Refer to: p4098
Note:
AI: Analog input
This parameter is not saved when data is backed-up (p0971, p0977).
02
DI 2 (X520.3)
Low
High
-
03
DI 3 (X520.4)
Low
High
-
04
DI 4 (X530.1)
Low
High
-
05
DI 5 (X530.2)
Low
High
-
06
DI 6 (X530.3)
Low
High
-
07
DI 7 (X530.4)
Low
High
-
08
DI/DO 8 (X541.2)
Low
High
-
09
DI/DO 9 (X541.3)
Low
High
-
10
DI/DO 10 (X541.4)
Low
High
-
11
DI/DO 11 (X541.5)
Low
High
-
p4097[0...1]
TB30 analog inputs simulation mode / TB30 AI sim_mode
TB30
Can be changed:
U, T
Access level:
2
Data type:
Integer16
Data set:
-
Function diagram:
9104
P-Group:
Terminals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 1
0
p4097[0...1]
TM31 analog inputs simulation mode / TM31 AI sim_mode
TM31
Can be changed:
U, T
Access level:
2
Data type:
Integer16
Data set:
-
Function diagram:
9566,
9568
P-Group:
Terminals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 1
0