Parameter list
Parameters
1-69
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the torque/force constant of the synchronous motor.
p0316 = 0: The torque/force constant is calculated from the motor data.
p0316 > 0: The selected value is used as torque/force constant.
Dependency:
Refer to: r0334
Note:
The parameter is automatically preset for motors from the motor list (p0301).
This parameter is not used for induction motors (p0300 = 1xx).
Description:
Induction motors:
Sets the rated motor magnetizing current.
For p0320 = 0.000 the magnetizing current is internally calculated and displayed in r0331.
Synchronous motors:
Sets the rated motor short-circuit current.
Note:
The parameter is automatically preset for motors from the motor list (p0301).
Description:
Sets the maximum motor speed/velocity.
Dependency:
Refer to: p1082
Note:
The parameter is automatically preset for motors from the motor list (p0301).
Description:
Set the maximum permissible motor current (e.g. de-magnetizing current for synchronous motors).
Note:
The parameter is automatically preset for motors from the motor list (p0301).
For induction motors, the parameter has not effect if p0323 is set to 0.
For synchronous motors, a value must always be entered for the maximum motor current.
p0323 is a motor data. The user-selectable current limit is entered into p0640.
p0316[0...n]
Motor torque constant / Mot kT
VECTOR
Can be changed:
C2, U, T
Access level:
1
Data type:
Floating Point
Data set:
MDS
Function diagram:
-
P-Group:
Motor
Units group:
TORQUE_PER_CURR
Unit selection:
-
Min Max
Factory
setting
0.00 [Nm/A]
100.00 [Nm/A]
0.00 [Nm/A]
p0320[0...n]
Motor rated magnetization current/short-circuit current / Mot I_mag_rated
VECTOR
Can be changed:
C2, U, T
Access level:
3
Data type:
Floating Point
Data set:
MDS
Function diagram:
5722
P-Group:
Motor
Units group:
CURRENT_AC_EFF
Unit selection:
-
Min Max
Factory
setting
0.000 [Aeff]
5000.000 [Aeff]
0.000 [Aeff]
p0322[0...n]
Maximum motor speed / Mot n_max
VECTOR
Can be changed:
C2
Access level:
2
Data type:
Floating Point
Data set:
MDS
Function diagram:
-
P-Group:
Motor
Units group:
SPEED_ROT
Unit selection:
-
Min Max
Factory
setting
0.0 [1/min]
210000.0 [1/min]
0.0 [1/min]
p0323[0...n]
Maximum motor current / Mot I_max
VECTOR
Can be changed:
C2
Access level:
2
Data type:
Floating Point
Data set:
MDS
Function diagram:
5722
P-Group:
Motor
Units group:
CURRENT_AC_EFF
Unit selection:
-
Min Max
Factory
setting
0.00 [Aeff]
20000.00 [Aeff]
0.00 [Aeff]