![Siemens SINAMICS G List Manual Download Page 401](http://html.mh-extra.com/html/siemens/sinamics-g/sinamics-g_list-manual_378180401.webp)
PROFIBUS
Function diagrams
2-401
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Picture 2-24 2440 – Standard/manufacturer-specific receive telegram interconnection
- 2440 -
8
7
6
5
4
3
2
1
fp_S01_2440_en.vsd
DO: VECTOR
SINAMICS G
17.12.04
V02.02.00
PROFIBUS - standard/manufacturer-specific receive telegram interconnecti
o
n
Function diagram
PROFIBUS
receive telegram
r2090...r2095 bit
r2050[0...15] WORD
r2060[0...14] DWORD
Telegram assignment
according to p0922
[2420]
...
X126
PROFIBUS
Signal receivers for PZD receive signals
Signal
STW1
NSOLL_A
<2>
PROFIBUS sampling time
Refer to [1020.7]
<3>
PROFIdrive
Signal No.
1
5
Meaning
Control word 1 for telegram 1 ... 106
Speed setpoint A (16-bit)
Interconnection
paramete
r
(bit serial)
p1070
<1>
Functio
n
chart
[2442]
[3030.2]
Data type
U16
I16
Normalization
-
4000 hex p2000
Drive object
Header
Trailer
<1>
When selecting a standard telegram or a manufacturer-specific telegram using p0922, these interconnection parameters of the
command data set CDS are automatically set to 0.
<2>
Data type according to to the PROFIdrive profile: I16 = Integer16, I32 = Integer32, U16 = Unsigned16, U32 = Unsigned32
<3>
Display parameters for receive data according to [2460].