Parameter list
Parameters
1-119
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Sets the signal source to select the drive data set, bit 4 (DDS, bit 4).
Dependency:
Refer to: r0051, r0837
Description:
Displays the command data set (CDS) selected using p0810 ... p0813.
Dependency:
Refer to: r0050, p0810, p0811, p0812, p0813
Note:
The currently effective command data set is displayed in r0050.
Description:
Displays the drive data set (DDS) selected using p0820 ... p0824.
Dependency:
Refer to: r0051, p0820, p0821, p0822, p0823, p0824
Description:
Sets the signal source for control word 1 bit 0 (ON/OFF1).
Recommenda-
tion:
When the signal source is set, this does not trigger a response - but only a signal change of the source.
p0824[0...n]
BI: Drive data set selection DDS bit 4 / DDS select., bit 4
VECTOR
Can be changed:
C2, T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
8565
P-Group:
Data sets
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0
r0836
CO/BO: Command data set CDS selected / CDS selected
VECTOR
Can be changed:
-
Access level:
2
Data type:
Unsigned8
Data set:
-
Function diagram:
1530,
2578
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
CDS selection bit 0
Off
On
-
01
CDS selection bit 1
Off
On
-
02
CDS selection bit 2
Off
On
-
03
CDS selection bit 3
Off
On
-
r0837
CO/BO: Drive data set DDS selected / DDS selected
VECTOR
Can be changed:
-
Access level:
2
Data type:
Unsigned8
Data set:
-
Function diagram:
8565
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
DDS selection bit 0
Off
On
-
01
DDS selection bit 1
Off
On
-
02
DDS selection bit 2
Off
On
-
03
DDS selection bit 3
Off
On
-
04
DDS selection bit 4
Off
On
-
p0840[0...n]
BI: ON/OFF1 / ON/OFF1
VECTOR
Can be changed:
T
Access level:
3
Data type:
Unsigned32
Data set:
CDS
Function diagram:
2501,
8920
P-Group:
Commands
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
0