![Siemens SINAMICS G List Manual Download Page 319](http://html.mh-extra.com/html/siemens/sinamics-g/sinamics-g_list-manual_378180319.webp)
Parameter list
Parameters
1-319
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Description:
Using this correction time, the valve lockout time in phase V (p1829) is compensated for a negative phase current
for the particular motor module. This therefore takes into account a spread in the valve lockout times of motor mod-
ules in a parallel circuit configuration.
Dependency:
Refer to: p1829
Description:
Using this correction time, the valve lockout time in phase W (p1830) is compensated for a positive phase current
for the particular motor module. This therefore takes into account a spread in the valve lockout times of motor mod-
ules in a parallel circuit configuration.
Dependency:
Refer to: p1830
Description:
Using this correction time, the valve lockout time in phase W (p1830) is compensated for a positive phase current
for the particular motor module. This therefore takes into account a spread in the valve lockout times of motor mod-
ules in a parallel circuit configuration.
Dependency:
Refer to: p1830
Description:
Ring buffer for faults and alarms that have occurred from power modules connected in parallel (motor module,
active line infeed, voltage sensing module).
Displays the fault/alarm code.
Dependency:
Refer to: r7101, r7102, r7103
Note:
The last fault case that occurred is documented in index 0.
The parameter is reset to 0 at POWER ON.
p7043[0...n]
Parallel circuit configuration, valve lockout time correction, phase V negative / Comp
t_interl Vneg
VECTOR (Parallel)
Can be changed:
U, T
Access level:
4
Data type:
Floating Point
Data set:
PDS
Function diagram:
-
P-Group:
Modulation
Units group:
TIME_M6
Unit selection:
-
Min Max
Factory
setting
0.00 [µs]
1000000.00 [µs]
0.00 [µs]
p7044[0...n]
Parallel circuit configuration, valve lockout time correction, phase W positive / Comp
t_interl Wpos
VECTOR (Parallel)
Can be changed:
U, T
Access level:
4
Data type:
Floating Point
Data set:
PDS
Function diagram:
-
P-Group:
Modulation
Units group:
TIME_M6
Unit selection:
-
Min Max
Factory
setting
0.00 [µs]
1000000.00 [µs]
0.00 [µs]
p7045[0...n]
Parallel circuit configuration, valve lockout time correction, phase W negative /
Comp t_interl Wneg
VECTOR (Parallel)
Can be changed:
U, T
Access level:
4
Data type:
Floating Point
Data set:
PDS
Function diagram:
-
P-Group:
Modulation
Units group:
TIME_M6
Unit selection:
-
Min Max
Factory
setting
0.00 [µs]
1000000.00 [µs]
0.00 [µs]
r7100[0...99]
Parallel circuit configuration, ring buffer fault/alarm code / Fault/alarm code
VECTOR (Parallel)
Can be changed:
-
Access level:
3
Data type:
Unsigned32
Data set:
-
Function diagram:
-
P-Group:
Displays, signals
Units group:
-
Unit selection:
-
Min Max
Factory
setting
- -
-