Parameters
Parameter list
1-234
Siemens AG 2004 All Rights Reserved
SINAMICS G List Manual, Edition 12.2004
Note:
The master control is used from the commissioning software (drive control panel) and from the advanced operator
panel (AOP, local mode).
Description:
Sets the processing mode for PROFIBUS STW1.10 "Control from PLC".
Generally, control world 1 is received with the first PROFIBUS receive word (PZD1) (this is in conformance to the
PROFIdrive profile). The behavior of STW1.10 = 0 corresponds to that of the PROFIdrive profile. For other applica-
tions that deviate from this, the behavior can be adapted using this particular parameter.
Values:
0:
Freeze setpoints and continue to process sign-of-life
1:
Freeze setpoints and sign-of-life
2:
Setpoints are not frozen
Note:
If the STW1 is not transferred according to the PROFIDRIVE profile with PZD1 (with bit 10 "control by the PLC"),
then P2037 should be set to 2.
Description:
The serial interface for the debug monitor is COM1 (X140) or COM2 (internal).
Value = 0: COM2 (internal)
Value = 1: COM1 (X140), PPI is de-activated
Note:
A change only becomes effective after a POWER ON.
Bit field:
Bit
Signal name
0 signal
1 signal
FP
00
ON/OFF1
No
Yes
-
01
OC / OFF2
No
Yes
-
02
OC / OFF3
No
Yes
-
03
Enable operation
No
Yes
-
04
Enables the ramp-function generator
No
Yes
-
05
Start ramp-function generator
No
Yes
-
06
Enable speed setpoint
No
Yes
-
07
Acknowledge fault
No
Yes
-
08
Jog bit 0
No
Yes
3030
09
Jog bit 1
No
Yes
3030
10
Master ctrl by PLC
No
Yes
-
11
Direction reversal
No
Yes
-
12
Enable speed controller
No
Yes
-
13
Motorized potentiometer, raise
No
Yes
-
14
Motorized potentiometer, lower
No
Yes
-
15
CDS bit 0
No
Yes
-
p2037
PROFIBUS STW1.10 = 0 mode / PB STW1.10=0 mode
VECTOR
Can be changed:
T
Access level:
3
Data type:
Integer16
Data set:
-
Function diagram:
-
P-Group:
Communication
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 2
0
p2039
Select debug monitor interface / Sel. debug monitor
CU
Can be changed:
U, T
Access level:
4
Data type:
Unsigned16
Data set:
-
Function diagram:
-
P-Group:
Communication
Units group:
-
Unit selection:
-
Min Max
Factory
setting
0 1
0